Stroking a valve moves the process. Agree every test with operations, isolate and depressurise where needed, and keep hands clear of the stem and linkages. Positioner menus and settings vary by make: follow the manufacturer's manual.
Pre-checks
- Nameplate vs datasheet: tag, size, rating, trim, Cv, fail action (fail open / closed / last), actuator type and air supply range.
- Flow direction arrow matches the line.
- Air supply: filter regulator set to the actuator's rated pressure (from the nameplate), clean dry air, drain the filter.
- Tubing tight; no leaks at fittings (listen and use leak spray).
- Mechanical: stem connector tight, travel indicator and scale correct, linkage/feedback arm secure.
Positioner calibration
- Check the action setting: direct (4 mA = closed) or reverse (4 mA = open), as the loop requires.
- Run the positioner's automatic calibration (auto-stroke) with the valve isolated from the process or agreed with operations. It finds the end stops.
- Check the tuning (gain / speed) the auto-calibration chose. A valve that overshoots or hunts may need a lower gain.
- Set any travel cut-offs (tight shut-off below e.g. 1 %) only if the process needs them, and record them.
- Save and record the configuration.
Stroke test
Apply 4, 8, 12, 16 and 20 mA going up, then back down, and record the actual travel at each step:
| Signal | Expected travel (direct) | Typical tolerance |
|---|---|---|
| 4 mA | 0 % | ± 1 % of travel |
| 8 mA | 25 % | ± 1–2 % |
| 12 mA | 50 % | ± 1–2 % |
| 16 mA | 75 % | ± 1–2 % |
| 20 mA | 100 % | ± 1 % |
The difference between the up and down readings at the same point is the hysteresis / deadband. Small steps (0.5–1 %) show whether the valve moves smoothly or jumps.
The Valve Stroke Check app builds the table and pass/fail for you; see also Valve Stroke Testing.
Fail-action, limit switches and solenoids
- Air failure: isolate the air supply. The valve must go to its fail position in the expected time.
- Signal failure: disconnect the mA signal. Most positioners drive to the fail position too.
- Solenoid (trip) valve: de-energise it and check the valve trips; time the stroke if the safety requirements specify it. The Solenoid Coil Check app helps confirm the coil is energised.
- Limit switches: set the open and closed switches so they change state just before the end of travel, and check the indication in the DCS.
Troubleshooting in service
| Symptom | Likely cause | Check / fix |
|---|---|---|
| PV cycles in a slow sawtooth, controller output a square wave | Stiction (static friction): packing too tight, damaged stem or trim | Small step test in manual; adjust packing per manufacturer; service trim |
| Valve hunts around setpoint | Positioner gain too high, or controller tuning | Put loop in manual: if it stops, it's tuning; if not, positioner |
| Won't fully close / passing | Seat damage, travel not reaching seat, wrong bench set | Stroke to 0 % and check travel; seat leakage test |
| Slow to move | Low air supply, blocked filter, small tubing, booster setting | Supply pressure at the positioner during stroking |
| Moves but wrong position | Feedback linkage loose or slipped | Re-fit linkage and re-calibrate |
| Packing leaking | Packing worn or loose | Tighten evenly per manual or replace; don't over-tighten (stiction) |
| Noise, vibration, damage downstream | Cavitation or flashing (liquids) or high velocity | Check sizing: see the Control Valve Cv app |
A level loop cycled continuously, even after the controller was detuned. In manual, a 0.5 % output step didn't move the valve; a 2 % step made it jump 1.5 %. The packing had been over-tightened during maintenance. After the packing was re-adjusted to the manufacturer's value, the valve followed 0.5 % steps and the loop settled.
Seat leakage
Seat leakage is specified by class (ANSI/FCI 70-2): for example Class IV for metal seats in general service, Class V for tighter metal-seated shut-off and Class VI for soft-seated (bubble-tight) valves. Check the class on the datasheet before deciding a valve is "passing": a Class IV valve is allowed a small leak.