Measurement / Flow meter commissioning

Flow Meter Commissioning: Mag, Coriolis, Vortex & DP

Most flow meter problems are installation problems: a part-full pipe, a missing earth, a meter zeroed with flow running. Commission each type against a short checklist and most of them never happen.

Field work needs a valid permit, isolation and the site's procedures. Tell operations before you touch a loop that feeds control or a safety system, and put the loop in manual or bypass only with their agreement. Device menus, limits and tolerances vary by make and model: always check the manufacturer's manual.

Checks for every flow meter

  • Datasheet vs nameplate: tag, size, flange rating, material, range, units, output and power all match.
  • Flow direction: the arrow on the body points with the flow.
  • Range and units are the same in the meter and in the control system (and mass vs volume vs standard volume is clear).
  • Output: loop check the 4–20 mA and pulse/frequency outputs with the meter's simulation function. See Loop Checking.
  • Low-flow cut-off is set so the reading is zero at no flow, but not so high that it hides real low flow.
  • First run: compare with a second measurement: tank level change, a check meter, or a pump curve.

Magnetic flow meters

CheckWhy
Liquid is conductive (typically at least about 5 µS/cm; check the data sheet)A mag meter cannot measure oils, hydrocarbons or very pure water
Pipe always full at the meterA part-full pipe reads high and noisy; mount in a rising line or low point
Earthing / grounding rings fitted for plastic or lined pipeWithout a reference to the liquid the signal is noisy or offset
Straight run (typically about 5D upstream, 2D downstream; check manual)Bends and valves distort the profile
Electrodes horizontal (not at top or bottom)Air at the top or solids at the bottom cover the electrodes
Empty-pipe detection setGives a clear alarm rather than a false reading
Field example: mag reads 40 % with the pump off
A new mag meter on a vertical downward line read flow with the pump stopped. The line drained, the meter was part-empty, and the electrodes picked up noise. Moving the meter to the rising section of the line fixed it.

Coriolis meters

  1. Install as the manual shows: for liquids usually tubes down (so gas can escape), for gas tubes up (so liquid drains).
  2. Support the pipe on both sides; don't let the meter carry pipe stress.
  3. Fill the meter completely and run flow for a while to purge gas and reach process temperature.
  4. Stop the flow with a tight-shut valve downstream (meter stays full and pressurised).
  5. Run the zero adjustment. Never zero with flow running or with the meter part-empty.
  6. Check density reads sensibly (for example about 1000 kg/m³ for water at 20 °C). A wrong density points to gas in the liquid.

Entrained gas or bubbles are the most common Coriolis problem: unstable flow and low density readings, and the drive gain rises. Fix the process (back-pressure, location) rather than the meter.

Vortex meters

  • Needs a minimum velocity / Reynolds number. Below it the meter reads zero, so it suits steady, moderate-to-high flows, not low flows or start-up.
  • Needs longer straight runs than most meters (often 15–20D or more upstream after bends and reducers; check the manual).
  • Pipe vibration can create a false signal at no flow. Check the reading with the line isolated; adjust the filter/low-flow cut-off per the manual.
  • Gasket must not stick into the bore: it disturbs the vortex street.

DP flow (orifice, venturi, nozzle)

  • Orifice orientation: sharp edge facing upstream; tab marked "inlet" on the upstream side.
  • Bore and β match the sizing calculation. Check the stamped bore on the plate tab.
  • Impulse lines: liquids: taps on the side, transmitter below; gas: taps on top, transmitter above; steam: condensate pots at equal height, legs filled.
  • Square root in one place only (transmitter or DCS).
  • Zero check with the manifold equalised.
Q = Qmax × √(ΔP / ΔPmax) Example: ΔP range 0–250 mbar, Qmax 100 m³/h, measured 62.5 mbar → 100 × √0.25 = 50 m³/h

Size or check the element with the DP Primary Element app; troubleshoot the transmitter with Transmitter Troubleshooting.

Quick fault table

SymptomMagCoriolisVortexDP
Reads flow at no flowPart-full pipe, noise, poor earthZero done badly, pipe stressVibrationZero shift, passing equaliser
Reads lowElectrode coatingGas entrainmentBelow minimum velocityLeaking high side, worn orifice edge
NoisySolids, air, poor earthGas / two-phase flowSwirl, short straight runPulsation, gas in liquid legs
Reads zeroEmpty pipeEmpty tube, drive faultBelow cut-offEqualiser open, plugged lines