Field work needs a valid permit, isolation and the site's procedures. Tell operations before you touch a loop that feeds control or a safety system, and put the loop in manual or bypass only with their agreement. Device menus, limits and tolerances vary by make and model: always check the manufacturer's manual.
Calibrate the parts separately
- Transmitter: disconnect the sensor and inject a known resistance (RTD) or millivolt (thermocouple) from a calibrator. This checks the electronics and the range.
- Sensor: put the sensor in a dry block or bath next to a reference probe and compare. This checks the element.
- Loop: with sensor and transmitter connected, compare the DCS reading against the reference. This catches wiring and configuration errors.
RTD (Pt100) checks
A Pt100 is 100 Ω at 0 °C and about 138.5 Ω at 100 °C, roughly 0.385 Ω per °C. Useful reference values (IEC 60751):
| Temperature | Pt100 resistance |
|---|---|
| −50 °C | 80.31 Ω |
| 0 °C | 100.00 Ω |
| 50 °C | 119.40 Ω |
| 100 °C | 138.51 Ω |
| 200 °C | 175.86 Ω |
| 300 °C | 212.05 Ω |
| IEC 60751 class | Tolerance |
|---|---|
| AA | ± (0.10 + 0.0017 |t|) °C |
| A | ± (0.15 + 0.002 |t|) °C |
| B | ± (0.30 + 0.005 |t|) °C |
A Pt100 was wired 2-wire with 1 Ω total lead resistance. The transmitter sees 1 Ω extra, about 1 / 0.385 = 2.6 °C high. Converting to 3-wire (or 4-wire) cancels most of the lead resistance.
- Open element: reading goes to full scale or the transmitter flags a sensor fault.
- Short or moisture in the sheath: reading low and unstable; check insulation resistance between element and sheath (with the transmitter disconnected).
Thermocouple checks
A thermocouple produces a small voltage proportional to the difference between the hot (measuring) junction and the cold (reference) junction at the transmitter terminals. The transmitter adds cold-junction compensation (CJC).
| Fault | What you see | Check |
|---|---|---|
| Extension wire reversed | Reading falls when temperature rises, or reads low by about twice the terminal temperature | Polarity at every joint: in IEC colours the negative is white |
| Copper wire used instead of extension wire | Error that changes with ambient temperature | Use the matching extension or compensating cable all the way |
| Wrong type configured (K vs J) | Large error that grows with temperature | Type in the transmitter vs sensor tag |
| Open thermocouple | Upscale or downscale burnout per configuration | Continuity of the loop of wire |
| Ageing / drift at high temperature | Slowly reads wrong after months at high temperature | Compare with a reference in a dry block; replace if out of tolerance |
Typical type K tolerance (IEC 60584 class 2) is ±2.5 °C or ±0.0075·|t|, whichever is larger. Read more in RTD vs Thermocouple.
Transmitter calibration procedure
- Record the tag, range, sensor type and wiring (2/3/4-wire or TC type) from the datasheet.
- Disconnect the sensor. Connect the calibrator in resistance (RTD) or mV/TC simulation mode. For TC simulation, use the calibrator's own CJC or a matching wire to the terminals.
- Connect a mA meter in the loop (or read the transmitter's output with a calibrator).
- Apply 0, 25, 50, 75 and 100 % of the range going up, then back down. Record the mA at each point.
- Calculate the error in % of span at each point and compare with the tolerance.
- If out of tolerance, do a sensor trim / output trim as the manual describes, then repeat the test and record As-left.
- Reconnect the sensor, check the reading is sensible, and return the loop to operations.
Sensor check in a dry block
- Use an insertion depth of at least 10–15 times the sheath diameter so the tip is not cooled by the air above the block.
- Put the reference probe in the same insert, as close as possible to the sensor under test.
- Wait for stability at each point (often several minutes). Rushing is the most common source of error.
- Test at least two points across the working range, for example 0 °C (ice point or block) and near the normal operating temperature.
A tank temperature read 3 °C higher than the local thermometer. Transmitter test with a resistance source: within 0.1 °C. Sensor in a dry block: within 0.2 °C. The remaining error was found in the wiring: a 2-wire connection on a 3-wire configured transmitter with a long cable. Correcting the third core removed the error.
Records
Record As-found and As-left at every point, the reference standard used (with its certificate number and due date), ambient temperature, date and technician. As-found data is what tells you whether the calibration interval is right.